Table of Contents
Understanding Step Down Transformers
| SC(B)11 | Rated capacity (KVA) | Voltage combination(KV) | No-load losses(W) | Load losses(W) | No-load current (%) | Short-circuit impedance (%) |
| SC11-30 | 30 | 6,6.3,6.6,10,11/0.4 | 180 | 710 | 2.4 | 4.0 |
| SC11-50 | 50 | 6,6.3,6.6,10,11/0.4 | 250 | 1000 | 2.4 | 4.0 |
| SC11-80 | 80 | 6,6.3,6.6,10,11/0.4 | 340 | 1380 | 1.8 | 4.0 |
| SC11-100 | 100 | 6,6.3,6.6,10,11/0.4 | 360 | 1570 | 1.8 | 4.0 |
| SC11-125 | 125 | 6,6.3,6.6,10,11/0.4 | 420 | 1850 | 1.6 | 4.0 |
| SCB11-160 | 160 | 6,6.3,6.6,10,11/0.4 | 490 | 2130 | 1.6 | 4.0 |
| SCB11-200 | 200 | 6,6.3,6.6,10,11/0.4 | 560 | 2530 | 1.4 | 4.0 |
| SCB11-250 | 250 | 6,6.3,6.6,10,11/0.4 | 650 | 2760 | 1.4 | 4.0 |
| SCB11-315 | 315 | 6,6.3,6.6,10,11/0.4 | 790 | 3470 | 1.2 | 4.0 |
| SCB11-400 | 400 | 6,6.3,6.6,10,11/0.4 | 880 | 3990 | 1.2 | 4.0 |
| SCB11-500 | 500 | 6,6.3,6.6,10,11/0.4 | 1050 | 4880 | 1.2 | 4.0 |
| SCB11-630 | 630 | 6,6.3,6.6,10,11/0.4 | 1210 | 5880 | 1.0 | 4.0 |
| SCB11-630 | 630 | 6,6.3,6.6,10,11/0.4 | 1170 | 5960 | 1.0 | 6.0 |
| SCB11-800 | 800 | 6,6.3,6.6,10,11/0.4 | 1370 | 6960 | 1.0 | 6.0 |
| SCB11-1000 | 1000 | 6,6.3,6.6,10,11/0.4 | 1590 | 8130 | 1.0 | 6.0 |
| SCB11-1250 | 1250 | 6,6.3,6.6,10,11/0.4 | 1880 | 9690 | 1.0 | 6.0 |
| SCB11-1600 | 1600 | 6,6.3,6.6,10,11/0.4 | 2210 | 11730 | 1.0 | 6.0 |
| SCB11-2000 | 2000 | 6,6.3,6.6,10,11/0.4 | 2720 | 14450 | 0.8 | 6.0 |
| SCB11-2500 | 2500 | 6,6.3,6.6,10,11/0.4 | 3200 | 17170 | 0.8 | 6.0 |
Step down transformers play a crucial role in electrical engineering by converting high voltage electricity to a lower voltage level. This process is essential for distributing electricity safely and efficiently to residential and commercial buildings. In essence, these transformers allow for the safe usage of electrical appliances that operate at lower voltages.
The design of a step down transformer involves a primary coil and a secondary coil, with the primary coil having more turns than the secondary. This configuration ensures that the voltage is reduced while maintaining the power levels. High-quality step down transformers are vital components in various applications, including renewable energy systems and industrial machinery, ensuring consistent performance and reliability.
100 kVA Transformers in Demand
The 100 kVA transformer is one of the most commonly used sizes in both industrial and commercial settings. Its capacity makes it ideal for powering medium-sized facilities, allowing for efficient energy distribution without excessive energy loss. As businesses expand, the demand for reliable transformers like the 100 kVA unit continues to grow, making it a staple in the electrical supply industry.

Manufacturers in China have recognized this trend and are producing a wide range of 100 kVA transformers designed to meet international standards. These products are often characterized by their high efficiency, durability, and cost-effectiveness. Many companies export these transformers globally, contributing significantly to the energy infrastructure in various countries.
High-Quality Manufacturing in China
China has established itself as a leading manufacturer of electrical equipment, including step down transformers and high-capacity units like the 100 kVA transformer. The country’s extensive manufacturing capabilities and technological advancements enable the production of high-quality transformers that meet global standards.
| SC(B)10 | Rated capacity (KVA) | Voltage combination(KV) | No-load losses(W) | Load losses(W) | No-load current (%) | Short-circuit impedance (%) |
| SC10-30 | 30 | 6,6.3,6.6,10,11/0.4 | 190 | 710 | 2.4 | 4.0 |
| SC10-50 | 50 | 6,6.3,6.6,10,11/0.4 | 270 | 1000 | 2.4 | 4.0 |
| SC10-80 | 80 | 6,6.3,6.6,10,11/0.4 | 370 | 1380 | 1.8 | 4.0 |
| SC10-100 | 100 | 6,6.3,6.6,10,11/0.4 | 400 | 1570 | 1.8 | 4.0 |
| SC10-125 | 125 | 6,6.3,6.6,10,11/0.4 | 470 | 1850 | 1.6 | 4.0 |
| SCB10-160 | 160 | 6,6.3,6.6,10,11/0.4 | 550 | 2130 | 1.6 | 4.0 |
| SCB10-200 | 200 | 6,6.3,6.6,10,11/0.4 | 630 | 2530 | 1.4 | 4.0 |
| SCB10-250 | 250 | 6,6.3,6.6,10,11/0.4 | 720 | 2760 | 1.4 | 4.0 |
| SCB10-315 | 315 | 6,6.3,6.6,10,11/0.4 | 880 | 3470 | 1.2 | 4.0 |
| SCB10-400 | 400 | 6,6.3,6.6,10,11/0.4 | 980 | 3990 | 1.2 | 4.0 |
| SCB10-500 | 500 | 6,6.3,6.6,10,11/0.4 | 1160 | 4880 | 1.2 | 4.0 |
| SCB10-630 | 630 | 6,6.3,6.6,10,11/0.4 | 1350 | 5880 | 1.0 | 4.0 |
| SCB10-630 | 630 | 6,6.3,6.6,10,11/0.4 | 1300 | 5960 | 1.0 | 6.0 |
| SCB10-800 | 800 | 6,6.3,6.6,10,11/0.4 | 1520 | 6960 | 1.0 | 6.0 |
| SCB10-1000 | 1000 | 6,6.3,6.6,10,11/0.4 | 1770 | 8130 | 1.0 | 6.0 |
| SCB10-1250 | 1250 | 6,6.3,6.6,10,11/0.4 | 2090 | 9690 | 1.0 | 6.0 |
| SCB10-1600 | 1600 | 6,6.3,6.6,10,11/0.4 | 2450 | 11730 | 1.0 | 6.0 |
| SCB10-2000 | 2000 | 6,6.3,6.6,10,11/0.4 | 3050 | 14450 | 0.8 | 6.0 |
| SCB10-2500 | 2500 | 6,6.3,6.6,10,11/0.4 | 3600 | 17170 | 0.8 | 6.0 |

Quality control is a priority for Chinese manufacturers, who implement rigorous testing procedures to ensure that each transformer performs optimally under various conditions. This commitment to quality not only enhances the lifespan of the transformers but also assures customers of their reliability. With a focus on innovation and sustainability, many Chinese companies are now incorporating advanced materials and technologies into their manufacturing processes, resulting in more efficient and environmentally friendly products.